The temperature of refrigerant gas above its boiling point at the evaporator exit. Critical for proper system charge and compressor protection.

Superheat is the temperature difference between the refrigerant gas leaving the evaporator coil and the refrigerant’s boiling point at that pressure. It’s measured in degrees F, typically 8-12°F for a properly charged AC system.

Why it matters: liquid refrigerant entering the compressor is catastrophic — it doesn’t compress and can destroy the compressor. Superheat ensures all the refrigerant has fully evaporated to gas before reaching the compressor. Too little superheat = liquid floodback risk. Too much superheat = system is undercharged and inefficient.

What superheat readings tell us

  • 0-5°F superheat — danger zone. Possible liquid floodback. Overcharged or TXV problem.
  • 8-12°F superheat — normal, target range for most systems
  • 15-25°F superheat — undercharged or restricted refrigerant flow
  • 30+°F superheat — significantly undercharged. Refrigerant leak likely.

Measuring superheat (and subcool) is what separates a proper commissioning from “topping off the freon.” It’s how we know the system is actually performing as designed, not just guessing.

Related: Subcool, Refrigerant, TXV, Compressor.